dc.date.updated2022-07-29T16:57:59Z
dc.description.abstractPower transformers and their performance and reliability in electric power networks are important research issues of power systems. Much information has already been collected and reported; however, it is rare to report comparisons of transformer service performance under different geographical locations and working conditions. CIGRE Working Group A2.37 collected information on 964 transformer failures from 58 utilities and 21 countries covering the period from 1996 to 2009. The main failure modes included failures in windings, tap changers, bushings, insulation, and core. As estimated, based on available literature, nearly 50% of the failures could be related to transformer windings and insulation. This collective paper summarizes experiences from the use of diagnostic tools based on frequency domain measurements at different geographical regions of the world. It starts with a short introduction to response measurements in frequency domain for condition assessment of transformers; then theoretical backgrounds of the two widely used response measurements, namely Frequency Dielectric Spectroscopy (FDS) and Frequency Response Analysis (FRA), are presented. Afterward details of tested transformers and measurement procedures are described for which selected set of FDS and FRA measurement results are analysed for respectively elucidating their potential in assessment of moisture content, ageing degree and fault identi cation.en_GB
dc.identifier.citationNo. 22en_GB
dc.identifier.urihttp://hdl.handle.net/10871/130501
dc.identifierORCID: 0000-0001-6039-8127 (Matharage, S)
dc.language.isoenen_GB
dc.publisherCIGREen_GB
dc.relation.urlhttps://cse.cigre.org/cse-n022/frequency-domain-measurements-for-diagnosis-of-power-transformers-experiences-from-australia-malaysia-sri-lanka-and-uken_GB
dc.rights© 2021 CIGREen_GB
dc.subjectTransformeren_GB
dc.subjectcondition assessmenten_GB
dc.subjectfrequency dielectric spectroscopyen_GB
dc.subjectfrequency response analysisen_GB
dc.subjectmoistureen_GB
dc.subjectwinding faulten_GB
dc.subjectmechanical faulten_GB
dc.titleFrequency Domain Measurements for Diagnosis of Power Transformers: Experiences from Australia, Malaysia, Sri Lanka and UKen_GB
dc.typeArticleen_GB
dc.date.available2022-08-24T09:15:56Z
dc.descriptionThis is the author accepted manuscript. The final version is available from CIGRE via the link in this recorden_GB
dc.identifier.eissn2426-1335
dc.identifier.journalCIGRE Science and Engineeringen_GB
dc.rights.urihttp://www.rioxx.net/licenses/all-rights-reserveden_GB
dcterms.dateAccepted2021-09-17
rioxxterms.versionAMen_GB
rioxxterms.licenseref.startdate2021-10-01
rioxxterms.typeJournal Article/Reviewen_GB
refterms.dateFCD2022-07-29T16:58:02Z
refterms.versionFCDAM
refterms.dateFOA2022-09-20T14:31:54Z
refterms.panelBen_GB


Files in this item

This item appears in the following Collection(s)

Show simple item record