dc.description.abstractThis paper presents a methodology for developing efficient and effective operational, short time response to an unplanned failure event (e.g. a pipe burst or equipment failure) in a water distribution system (WDS). The proposed automated response methodology consists of isolating the failure event followed by the recovery of the affected system part by restoring the flows and pressures to normal conditions. The isolation is typically achieved by manipulating the nearby on/off valves. The recovery, which is the focus of this work, involves selecting an optimal combination of suitable operational interventions from a number of possible choices with the aim to reduce the negative impact of the failure (e.g. volume of water undelivered to consumers) over a pre-specified time horizon. The intervention options considered here include valve manipulations, changing the pressure reducing valve’s (PRV) outlet pressure, and installation and use of a temporary overland bypasses from a nearby hydrant(s) in an adjacent, unaffected part of the network. The optimal mix of interventions is identified by using a multi-objective optimization approach driven by the minimization of the negative impact on the consumers and the minimization of the corresponding number of operational interventions (which acts as a surrogate for operational costs). The above methodology has been applied to a real world water distribution network of C-Town. The results obtained demonstrate the effectiveness of the proposed methodology in identifying the Pareto optimal intervention strategies that could be ultimately presented to the control room operator for making a suitable decision in near real time.en_GB
dc.description.sponsorshipThe first author acknowledges the support of the Kurdistan Regional Government in Iraq, Ministry of High Education and Scientific Research, through Human Capacity Development Program (HCDP).en_GB
dc.identifier.citationVol. 144 (7).en_GB
dc.identifier.doi10.1061/(ASCE)WR.1943-5452.0000956
dc.identifier.urihttp://hdl.handle.net/10871/31214
dc.language.isoenen_GB
dc.publisherAmerican Society of Civil Engineersen_GB
dc.relation.sourceSupplemental Data Appendix S are available online in the ASCE Library (www .ascelibrary.org).en_GB
dc.rights© 2018 American Society of Civil Engineers.
dc.subjectWater distribution systemen_GB
dc.subjectoptimizationen_GB
dc.subjectpipe bursten_GB
dc.subjectresponseen_GB
dc.subjectinterventionen_GB
dc.subjectrecoveryen_GB
dc.subjecthydraulic solveren_GB
dc.titleReal-time operational response methodology for reducing failure impacts in water distribution systemsen_GB